Full system 10/10
Full system replacement Monday. Thank you for choosing LBA services!
Customer declined estimate
Met with Brian and he relayed to me that the furnace in the basement is not drafting properly and he would like to replace it as well as cap the flue pipe at the top of the chimney and move over to a 90% flue. Furn m/n 586P050-BA model 100, s/n 4188A00304 Input 50K, 70% natural draft Furn width x length 14 1/4” x 28 1/2” Plenum 19” x 12.75” Furn height 46 3/8” Furn sits 3.5” off of ground Concrete wall 16” 66 1/2” floor to first takeoff
.
W
W
W
W
Went for a furnace inspection today. Did a static pressure test, it failed. Did a carbon monoxide and gas leak test, no leaks. Combustion analysis test passed. Inducer motor amperage passed. Gas pressure and pressure switch passed. Exhaust flu is in good condition. Temperature split between the supply and return duct passed. Blower motor amperage passed and blower wheel is clean. Thank you for choosing LBA services!
Customer has pneumatic zoning system that was acting up and making a lot of noise from internal vacuum pump. Found that constant power switch to pump was in on position. Turned to off and tested system and everything was functioning normally.